Skip to main content
Brand Name: M-TEC
Model Name: WPS1052-AK
Model Structure (mono/split): Monobloc
Type: Brine to water
Rated heat output, Prated[kW] 48.00
Low temperature heat pump No
Seasonal Space Heating Efficiency, ηs [%] 160.00
Water heating efficiency, ηwh [%] N/A
General Details
Product index number 971425
Source of data Ecodesign declaration
First year of manufacture 2021
Final year of manufacture Current
Identification
Manufacturer's name M-TEC GmbH
Brand Name M-TEC
Model Name WPS1052-AK
Model Qualifier 400V
Model Structure Monobloc
Appliance ID
Basic Properties
Heat Pump Type Brine to water
Low Temperature Heat Pump No
Fuel Type Electricity
Indoor unit power supply 3-phase
Outdoor unit power supply N/A
Equipped with supplementary heater No
Heat pump combination heater No
Rated Air Flow [m3/h]
Space Heating EN Test Standard EN 14825
Space Heating Efficiency Class (medium temperature application) A++
Space Heating Efficiency Class (low temperature application) A+++
Seasonal space heating efficiency, ηs [%] (medium temperature application) 160
Seasonal space heating efficiency, ηs [%] (low temperature application) 214
Water Heating EN Test Standard N/A
Water Heating Efficiency Class N/A
Water Heating Efficiency, ηwh [%] N/A
Temperature Control (Capacity Control) Variable
Operation Limit Temperature, TOL [°C] -10
Heating Water Operation Limit Temperature WTOL [°C] 62
Heat Pump Test Data I.S. EN 14825
Low Temperature Application Condition, 35°C
Low Temperature Test Condition Yes
Degradation co-efficient 0.9
Test Condition - Low (35°C)
Tj A
(88%)
-7 °C
B
(54%)
2 °C
C
(35%)
7 °C
D
(15%)
12 °C
E
(100%)
TOL
Declared Heating Capacity (kW) 47.1 28.8 18.6 11.2 51.4
Coefficient of Performance (kW/kW) 4.6 5.4 6.17 5.67 4.34
Primary Energy Ratio (%) N/A N/A N/A N/A N/A
Intermediate Temperature Application Condition, 45°C
Intermediate Temperature Test Condition No
Medium Temperature Application Condition, 55°C
Medium Temperature Test Condition Yes
Degradation co-efficient 0.9
Test Condition - Medium (55°C)
Tj A
(88%)
-7 °C
B
(54%)
2 °C
C
(35%)
7 °C
D
(15%)
12 °C
E
(100%)
TOL
Declared Heating Capacity (kW) 42.5 25.8 17.9 10.5 N/A
Coefficient of Performance (kW/kW) 3.07 3.96 4.93 5.47 2.9
Primary Energy Ratio (%) N/A N/A N/A N/A N/A
High Temperature Application Condition, 65°C
High Temperature Test Condition No
F-Gas Details
F-Gas Name R410a
F-Gas Quantity 10
F-Gas GWP 2088
Record last updated
Details available from:

M-TEC GmbH
Pinsdorf
Upper Austria
Austria
+43 7612 20805

Mtec-systems.com

Return to HARP search